Communications failure for both types of stations shall be indicated at the pumping station and telemetered to and annunciated at the main Control Room at the WSSC Control Room as an alarm.

An indicating light for communications failure and manual reset button to reset the primary control shall be provided at the pumping station pump control panel. (Amended during 2019 codification; 28-ME-DG-02 § 23.5)