Skip to main content
Loading…
Article V. Electrical Service and Distribution
This article is included in your selections.
This section is included in your selections.

The service voltage shall be 480/277 volts, three-phase, four-wire or 208/120 volts, three-phase, four-wire.

Equipment voltage characteristics shall be as follows:

Equipment

Rating

Voltage

Phase

Motors

1/2 hp and below

120 V

1 ph

Motors

above 1/2 hp

480 V

(208 V

3 ph

3 ph)*

Unit Heaters

2 kW and below

208 V

(120 V

3 ph

1 ph)

Unit Heaters

3 kW and above

480 V

3 ph

Lighting

120 V

1 ph

*where 480 V is not available.