The starting system shall consist of a 24-volt battery system. The battery set shall consist of two heavy duty 12-volt, lead-acid batteries designated for such a use. The battery set shall preferably be located within the engine/generator set base.

Since the engine/generator set seldom runs long enough to maintain a full charge on the starting batteries, an adequately sized automatic battery charger of the solid state type shall be provided in a NEMA 4X pedestal mounted enclosure located near the engine/generator set. The charger shall be of the constant voltage, current limiting type. The charger shall float-charge the batteries and also provide an equalized charge. The battery charger shall include the following additional features: DC voltmeter and ammeter, AC input circuit breaker, DC output fuse, charger failure alarm contacts, and LED indications for AC input power “on,” charge mode, and equalize charge mode. (Design Guideline DG-08 § 18.2.3, dated August 2006)